© 2008 Schneider Electric
Parameter
|
Note:
The parameter settings include various
functions which depend on other functions.
Depending on the parameter setting, some
functions or objects may or may not be
displayed in the ETS.
● General brightness evaluation:
The current brightness can be determined by the
internal brightness sensor, by an external
communication object or by both dependencies. The
relationship between internal and external values can
be parametrised while doing this.
Communication objects
You can select the following communication objects:
General:
Parameter
For actual value correction you will need a luxmeter.
The measured values are then input into the
application software of the presence detector.
When intense sunlight is shining onto the reference
area or the installation location, the measurements
should not be taken. Under certain circumstances
darkening the room may improve the measurement
results.
● Movement block
Basic function of a movement block
A staircase timer is "integrated" into a movement
block. When the ambient brightness is too low and a
movement is detected, the movement block transmits
an ON telegram to the bus. When no further
movement is detected the staircase timer starts. An
OFF telegram is transmitted to the bus after a
parametrised time.
Brightness is measured only at the moment when
the first movement is detected. If further movement is
detected, an OFF telegram is not transmitted,
irrespective of brightness changes. The staircase
timer starts only when movement is no longer
detected, and an OFF telegram is transmitted after the
parametrised time period.
Block configuration
Up to five movement blocks are available. In the
default setting, block 1 is enabled.
Parameter
Movement detection
The device has a detection angle of 220°.
To suppress disturbance variables or if delayed
activation is required, a dead time for the start of
movement can be activated. The dead time is started
after movement has been detected (start of
movement). The start of movement action
(transmitting a telegram to the bus) can take place if a
movement is still detected within the movement time
after the dead time has elapsed.
In master mode or normal mode the movement time
corresponds to the staircase timer in the diagram
above. In slave mode or monitoring mode the
movement time corresponds to the cycle time. In
practice a large number of applications can be
implemented by means of the various blocks.
Block diagram of movement block
A block diagram clarifies the relationships between the
individual dependencies.
General
Parameter Setting
Safety pause via status feedback
object
Disabled
For OFF telegram
For ON and OFF telegram
Safety pause (1 - 20) seconds 1-20, preset: 2
Function Object name Type Prio Flags Behaviour
External
sensor
Actual value input 2
bytes
Low WCT
U
Transmit/
receive/
update
General
Parameter Setting
Actual value (brightness) From internal sensor
From object, actual value input
From internal sensor and object
Taking the separately measured
lux value (0% - 100%) into
account
0% - 100%, in 5% steps;
preconfiguration 50%
Block configuration
Parameter Setting
Movement block X Enabled
Disabled
ON
OFF
Switch object
Movement
Time
Time
Dead
Time
Movement
Time
Dead
Time
Movement
Time
Movement
Time
Movement
Time