© 2008 Schneider Electric
Movement evaluation
As has already been stated above, the movement
sensor input into movement detection.
The master trigger object is brightness-dependent and
with an ON telegram simulates a movement; an OFF
telegram is ignored.
The trigger object is brightness-independent and also
simulates a movement for an ON telegram . Whether
the trigger object can switch the lighting off early
when there is an OFF telegram can be parametrised.
|
Note:
The master trigger object and the trigger object
do not appear in the ETS until the device
operating mode has been set to "Master mode".
See "Block X, general" tab, parameter:
"Operating mode". The master/trigger object
ignores the dead time (for Dead time, see
above) and reacts without a delay. More
detailed information about the master/trigger
object may be found later on.
Communication objects
You can select the following communication objects:
Block X, general movement sensors:
Parameter
|
Note:
The parameter settings include various
functions which depend on other functions.
Depending on the parameter setting, some
functions or objects may or may not be
displayed in the ETS.
Move
Sensor
Master
Trigger
Brightness
sensor
Always-
dark obj.
Trigger obj.
Disable obj.
Movement
detection
Brightness obj.
Brightness
evaluation
Output obj.
1-4
Disable
function
Times
Telegrams
Function Object name Type Prio Flags Behaviour
Block X Range 1 byte Low WC Receive
Block X, general - movement
sensors
Parameter Setting
Advanced settings Enabled
Disabled
The following settings are only
visible when "Disabled".
Sensitivity (for all sensors) High
Medium
Low
Range adjustable Potentiometer
Parameter
Range
(only visible by "Parameter")
10% - 100% (in 10% steps)
preconfiguration: 100%
The following settings are only
visible when "Enabled".
Range object (for all sensors) Disabled
Enabled
Dead time, start of movement (for
all sensors)
Disabled
Enabled
Time base 1 min, 1s
Time factor (1 - 255) 3, (1-255)